Online UPS  



Model: HP990 (3:3)
40K~120K


Introduction:
HP990 high frequency UPS possess of double DSP control technology with high capability and complete digital control. Its performance is better the same rating product from other manufacturers at home and abroad in current market. Further more its price is absolutely competitive compared with international manufactureres.

Application field:
ISP (Internet Service Provider ), IDC(Internet Data Center), network control center/computer centre, the charge system, Bank/Bond settlement centre, business server, Industrial process control application, Office automation system and precision instruments ect.


Features :
Three phase in three phase out; support 380/400/415V,50/60Hz power grid systems
True online dual converstion; provide with high quality power (±0.5%)
Double DSP with complete digital control; make IGBT rectifier, inveter, charge, discharge and convertor be completely high frequency digital
UPS can carry 100% non-balance load, and half wave load;
Wide input voltage anti-jamming range(-40%~+20%) and frequency range(40~70Hz),adapt to bad power gird environment
Green power technology; High input power factor(0.99), low harmonic current(THDI<3%); energy-saving
Perfect output short circuit protection
1+1 redundant assistant power supply design
N+N redundant design for the cooling fan of the main power components
Online sense and protection function for components state: all of IGBT,SCR, fuse, fans ect states can be inspected on line and alarm by buzzer and LCD display
Intelligent battery management, prolong the battery life
Large LCD screen display, friendly Human-Machine Interface, thousands pieces of history record memorized
Blow front face in, blow upward out; It is convenient to install other matched cabinet side by side, and the back door can be installed against wall to save space;
Similar Modularize Design, easy maintenance
Complete Maintenance can be done from front, all components maintenance and replacement can be done from the front door, and don't need to move unit or take down the side door
Adopt air intake screened, and separate duct from inductance and module,Make sure no dust accumulated inner UPS, improving unit reliablity and prolonging the fan life.
Support up and down wire conection manner
Dispersive parallel technology; support redundant parallel(up to 6)and expansion online (Next version)
Digital circumfluence technology; small circumfluence; high reliable parallel (Next version)
Options---Main circuit backfeed protection, bypass backfeed protection, battery leakage protection, battery cold start function (Next version)


Specifications:

                                   Capacity
40KVA,60 KVA
Mains input
Input voltage
380V/400V ( Linear voltage )
Input Phase
Three phase four wire
P. F.
>0.99
Harmonic current (THDI)
<3%
Voltage range
+20%~-40%
Linear rating drop Between -20%~-40% and 100%~50%
Frequency range
40~70HZ
Bypass input
Input voltage
380/400/415V ( linear voltage )
Input voltage range
+20%~-50%
Input Phase
Three phasefour wire
Frequency range
40~70HZ
Output
Stable voltage precision
( balanceable load )
±0.5%
Dynamic voltage
in instantaneous change
±2% ( 0~100% load change )
Voltage aberration ( linear load )
THD<0.5% ( Phase voltage )
Voltage aberration ( Non-linear load )
THD<5% ( Phase voltage)
P.F.
0.8 ( lag)
Frequency track range
50Hz±3Hz
Frequency precision ( battery inverter )
±0.1%
3 phase difference
120±0.5° ( balanceable or un-balanceable load )
100% imbalance degree of un-balanceable load voltage
±3%
Frequency track speed
<1Hz/s
Inverter overload capability
105%(load <110%, transfer to bypass after 60minutes

111%<(load <125%, transfer to bypass and output after 10±0.1mintes

125%(load< 150%, transfer to bypass and output after 1 minute ;
Bypass overload capability
Run long time when 150% load

Hold on 100ms when load>1000%
System
System efficiency ( linear load)
91%
Battery inverter efficiency ( linear load )
91%
Display
LCD+LED
EMC/EMI
Conduction/radiation
FCC Part 15, Class A
Harmonic current
EC6 1000-3-12
Anti-jamming
I EN 6 1000-4-2 .3.4..6.8.9.11 Level III
, EN 6 1000-4-5 Level Ⅳ
Noise ( 1m )
<60dB
Insulated resistance
> 2M (500VDC)
Insulated intensity
(input, output against ground) 2820Vdc; electricity leakage is less than 3.5mA; no flashover 1min
Electricity surge protection
Meet IEC60664-1 Ⅳ installation requirement, bear 1.2/50us+8/20us mixed wave capability is not less than 6KV/3KA
Defence level
IP20
Battery quantity
38~42 pcs 12V battery
Installation
Wire connection
Up and down wire connection
top
back