Model: HP-YJ
Application field
For the purpose of traffic hinge, stadium and gymnasium, high buildings, tunnels, large entertainment centers, metallurgy, chemistry, electric power plants, mining and plants.
|
|
Category
YJ series
Capacity ranges between 0.5KW and 20KW,for lighting in emergency or accidental instance
YJS series
Capacity ranges between 5KW and 400KW. Besides providing lighting in emergency or accidental instance, this series can also be used for fire-fight elevators, rolling shutters, draught fans, water pumps and other inductive load or mixed load.
YJS/P series
Capacity ranges between 1KW and 800KW. This series is special power supply for connecting directly to electric motors, and can be used for fire-fight water pumps, draught fans, spray pumps and other pure inductive load.
Features
Self-adaptive load control technique with enhanced working reliability.
Smart battery charging and management to increase battery life.
LCD with Chinese interface for easy operation. Modularized design to simplify maintenance, and to improve system reliability.
RS485 communication port for connection to surveillance center to achieve remote control, communication, remote measurement, and linkage.
Using PLC as system control center to improve operation reliability and site adaptability.
Smart self-testing on stand-by status.
Fully automatic startup without human interference.
Changeable transfer time (from 0.25 to 10 seconds).
Startup by compulsive manual operation in emergency situations.
specifications
|
Model |
HP-YJ-0.5
KW |
HP-YJ-1
KW |
HP-YJ-1.5
KW |
HP-YJ-2
KW |
HP-YJ-2.5
KW |
HP-YJ-3-5KW |
HP-YJ-6-20KW |
Input |
DC Voltage
(V) |
48VDC(42VDC~68VDC) |
192VDC |
AC Voltage
(V) |
Single phase/220V±25% |
Single phase/220V±20%;
three phases/380V±25% |
Frequency
(Hz) |
50Hz±25% |
Output |
Current (A) |
2.2A |
4.5A |
6.8A |
9A |
11.3A |
|
Voltage |
Same as commercial power when in regular conditions |
220V±25% in emergency |
Frequency |
Same as commercial power in regular conditions, 50Hz±0.5% in emergency |
Same as commercial power in regular conditions, 50Hz±1% in emergency |
Others |
Transfer time |
0.25 to 10 seconds resettable,(less than 0.004 second if required) |
Output waveform |
Same as commercial power in regular conditions, sine wave in emergency |
Overload capacity |
Working properly when the load is 120% of designed capacity |
Backup time |
Longer than 90 minutes or customized endurance |
Audible noise |
Quiet on commercial power, <55dB in emergency mode |
Relative moisture |
LED、LCD Chinese interface, touch screen(optional) |
Environment temperature |
-20℃~40℃ |
Altitude height |
Below altitude 2000 meters |
Suitable load type |
Mainly for loads for lighting purpose |
weight |
20.5 Kg |
25Kg |
30Kg |
48Kg |
52Kg |
|
|
Dimensions
W×D×H (mm) |
600×215×650 |
600×215×1200 |
600×215×1400 |
800×600×1800 |
800×800×1800 |
Noise level |
45~60 dB |
|
|